Saturday, April 2, 2011

DUCTS AND PIPE SIZING IN HVAC SYSTEM

AR-461: BUILDING SCIENCE
By:
RAVINDAR KUMAR
Assistant Professor
Department of Architecture and Planning
NED University of Engineering and Technology
Karachi
LECTURE NO. 08
TOPIC:                                            DUCTS AND PIPE SIZING

INTRODUCTION:[1]
Ducts are used in heating, ventilation, and air conditioning (HVAC) to deliver and remove air. These needed airflows include, for example, supply air, return air, and exhaust air[2] Ducts also deliver, most commonly as part of the supply air, ventilation air. As such, air ducts are one method of ensuring acceptable indoor air quality as well as thermal comfort. A duct system is often called ductwork. Planning ('laying out'), sizing, optimizing, detailing, and finding the pressure losses through a duct system is called duct design.[3]

MATERIALS USED IN DUCT WORK:
Ducts can be made out of the following materials:

Galvanized mild steel is the standard and most common material used in fabricating ductwork.

POLYURETHANE AND PHENOLIC INSULATION PANELS (PRE-INSULATED AIR DUCTS):
Traditionally, air ductwork is made of sheet metal which is installed first and then lagged with insulation as a secondary operation. Ductwork manufactured from rigid insulation panels does not need any further insulation and is installed -kankermongool- in a single fix. Light weight and installation speed are among the features of pre-insulated aluminum ductwork, also custom or special shapes of ducts can be easily fabricated in the shop or on site.

The ductwork construction starts with the tracing of the duct outline onto the aluminum pre-insulated panel, then the parts are typically cut at 45 degree, bent if required to obtain the different fittings (i.e. elbows, tapers) and finally assembled with glue. Aluminum tape is applied to all seams where the external surface of the aluminum foil has been cut. A variety of flanges are available to suit various installation requirements. All internal joints are sealed with sealant.

Among the various types of rigid polyurethane foam panels available, a new water formulated panel stands out. In this particular panel, the foaming process is obtained through the use of water instead of the CFC, HCFC, HFC and HC (Hardcore) gasses. And most manufacturers of rigid polyurethane foam panels use normal pentane as foaming agent instead of the CFC, HCFC, HFC and HC gasses, so do manufacturers of rigid phenolic foam panels. A rigid phenolic insulation ductwork system is available and complies with the UL 181 standard for class 1 air ductwork.
Both polyurethane foam panels and phenolic foam panels are then coated with aluminum sheets on both sides, with outside aluminum thicknesses that can vary from 80 micrometers for indoor use to 200 micrometers for external use or high air pressure in order to guarantee the high mechanical characteristics of the duct, or then coated with aluminum sheets on inside, and coated with 200 micrometers sheet metal or pre-painted sheet metal on outside.

FIBERGLASS DUCT BOARD (PREINSULATED NON METALLIC DUCTWORK):
Fiberglass duct board panels provide built-in thermal insulation and the interior surface absorbs sound, helping to provide quiet operation of the HVAC system. The duct board is formed by sliding a specially-designed knife along the board using a straightedge as a guide; the knife automatically trims out a "valley" with 45° sides; the valley does not quite penetrate the entire depth of the duct board, providing a thin section that acts as a hinge. The duct board can then be folded along the valleys to produce 90° folds, making the rectangular duct shape in the fabricator's desired size. The duct is then closed with staples and special aluminum or similar 'metal-backed' tape. Commonly available duct tape should not be used on air ducts, metal, fiberglass, or otherwise, that are intended for long-term use; the adhesive on so called 'duct tape' dries and releases with time.

FLEXIBLE DUCTING:
Flexible ducts, known as flex, have a variety of configurations, but for HVAC applications, they are typically flexible plastic over a metal wire coil to make round, flexible duct. In the United States, the insulation is usually glass wool, but other markets such as Australia, use both polyester fibre and glass wool for thermal insulation. A protective layer surrounds the insulation, and is usually composed of polyethylene or metalised PET. Flexible duct is very convenient for attaching supply air outlets to the rigid ductwork. However, the pressure loss through flex is higher than for most other types of ducts. As such, designers and installers attempt to keep their installed lengths (runs) short, e.g., less than 15 feet or so, and to minimize turns. Kinks in flex must be avoided. Some flexible duct markets prefer to avoid using flexible duct on the return air portions of HVAC systems, however flexible duct can tolerate moderate negative pressures - the UL181 test requires a negative pressure of 200 Pa.[4]


FABRIC DUCT WORK:
Fabric ducting, also known as air socks, duct socks or textile ducts, are designed for even air distribution throughout the entire length. Usually made of special polyester material, fabric ducts can provide air to a space more effectively than a conventional exposed duct system. Fabric duct is a misnomer as "fabric duct" is actually an "air distribution device" and is not intended as a conduit (duct) for conditioned air. However, as it often replaces hard or metal ductwork it is easy to perceive it simply as duct. Fabric air dispersion systems, is the more definitive name. As they may be manufactured with venting or orifices for even air distribution along any length of the system, they commonly will provide a more even distribution and blending of the conditioned air in a given space. As "fabric duct" is used for air distribution, textile ducts are not rated for nor should they be used in ceilings or concealed attic spaces. Applications for fabric duct in raise floor applications; however, are available. Depending on the manufacturer, "fabric duct" is available in standard and custom colours with options for silk screening or other forms of appliqués. "Fabric duct", depending on the manufacturer, may be available in air permeable (porous) or non-porous fabric.
As a benchmark, a designer may make the determination of which fabric is more applicable by asking the question if the application would require insulated metal duct. If metal duct would be insulated in a given application or installation, air permeable fabric would be recommended as it will not commonly create condensation on its surface and can therefore be used where air is to be supplied below the dew point. Again; depending on the material and manufacturer, material that eliminates moisture may also be healthier and may also be provided with an active anti-microbial agent to inhibit bacteria growth. Porous material also tends to require less maintenance as it repels dust and other airborne contaminants.

DUCT SYSTEM COMPONENTS:
Besides the ducts themselves, complete ducting systems contain many other components.

VIBRATION ISOLATORS:
A duct system often begins at an air handler. The blowers in the air handlers can create substantial vibration and the large area of the duct system would transmit this noise and vibration to the inhabitants of the building. To avoid this, vibration isolators (flexible sections) are normally inserted into the duct immediately before and after the air handler. The rubberized canvas-like material of these sections allows the air handler to vibrate without transmitting much vibration to the attached ducts.

TAKE-OFFS:
Downstream of the air handler, the supply air trunk duct will commonly fork, providing air to many individual air outlets such as diffusers, grilles, and registers. When the system is designed with a main duct branching into many subsidiary branch ducts, fittings called take-offs allow a small portion of the flow in the main duct to be diverted into each branch duct. Take-offs may be fitted into round or rectangular openings cut into the wall of the main duct. The take-off commonly has many small metal tabs that are then bent to retain the take-off on the main duct; round versions are called spin-in fittings. Other take-off designs use a snap-in attachment method, sometimes coupled with an adhesive foam gasket to provide improved sealing. The outlet of the take-off then connects to the rectangular, oval, or round branch duct.

STACKS, BOOTS, AND HEADS:
Ducts, especially in homes, must often allow air to travel vertically within relatively thin walls. These vertical ducts are called stacks and are formed with either very wide and relatively thin rectangular sections or oval sections. At the bottom of the stack, a stack boot provides a transition from an ordinary large round or rectangular duct to the thin wall-mounted duct. At the top, a stack head can provide a transition back to ordinary ducting while a register head allows the transition to a wall-mounted air register.

VOLUME CONTROL DAMPERS:
Ducting systems must often provide a method of adjusting the volume of air flow to various parts of the system. VCDs (Volume Control Dampers - Not To Be confused with Smoke/Fire Dampers) provide this function. Besides the regulation provided at the registers or diffusers that spread air into individual rooms, dampers can be fitted within the ducts themselves. These dampers may be manual or automatic. Zone dampers provide automatic control in simple systems while VAVs allow control in sophisticated systems.
SMOKE/FIRE DAMPERS:
Smoke and Fire dampers are found in ductwork, where the duct passes through a firewall or fire curtain. Smoke dampers are automated with the use of a mechanical motor often referred to as an Actuator.

A probe connected to the motor is installed in the run of duct, and detects smoke within the duct system which has been extracted from a room, or which is being supplied from the AHU (Air Handling Unit) or elsewhere within the run. Once smoke is detected within the duct, the Actuator triggers the motor release and the smoke damper will automatically close until manually re-opened.

You will also find Fire dampers in the same places as smoke dampers, depending on the application of the area after the firewall. Unlike smoke dampers, they are not triggered by any electrical system, which is perfect in the event of an electrical failure where the Smoke dampers would fail to close. A fire damper is held open by a bar crossing the corrugated screen, which will break and allow the damper to close when air in the duct is above a certain temperature. This again will then have to be manually re-opened.

PLENUMS:
Plenums are the central distribution and collection units for an HVAC system. The return plenum carries the air from several large return grills (vents) to a central air handler. The supply plenum directs air from the central unit to the rooms which the system is designed to heat or cool.

TERMINAL UNITS:
While single-zone constant air volume systems typically don't have them, other types of air distribution systems often have terminal units in the branch ducts. Usually there is one terminal unit per thermal zone. Some types of terminal units are VAV 'boxes' of either single or dual duct, fan-powered mixing boxes of either parallel or series arrangement, and induction terminal units. Terminal units may also include either, or both, a heating or cooling coil.

AIR TERMINALS:
'Air terminals' are the supply air outlets and 'return' or 'exhaust air inlets'. For supply, diffusers are most common, but grilles, and for very small HVAC systems such as in residences, 'registers' are also used widely. Return or 'exhaust grilles' are used primarily for appearance reasons, but some also incorporate an air filter and are known as 'filter returns'.[5]

DUCT CLEANING:
The position of the U.S. Environmental Protection Agency (EPA) is that "If no one in your household suffers from allergies or unexplained symptoms or illnesses and if, after a visual inspection of the inside of the ducts, you see no indication that your air ducts are contaminated with large deposits of dust or mold (no musty odor or visible mold growth), having your air ducts cleaned is probably unnecessary."[6] Studies by the EPA and the Canadian Mortgage and Housing Corporation (CMHC) in the 1990s has lead CMHC to conclude that "duct cleaning will not usually change the quality of the air you breathe, nor will it significantly affect airflows or heating costs".[7]

SIGNS AND INDICATORS:
  • When cleaning, you need to sweep and dust your furniture more than usual.
  • After cleaning, there's still left over dust floating around the house that you can see.
  • After or during sleep you experience headaches, nasal congestion, or other sinus problems.
  • Rooms in your house have little or no air flow coming from the vents.
  • You're constantly getting sick or are experience more allergies than usual
  • When you turn on the furnace or air conditioner there's musty or stale odor
  • You're experiencing signs of sickness: fatigue, headache, sneezing, stuffy or running nose, irritability and nausea, dry or burning sensation in eyes, nose and throat.[8]

UNRESOLVED ISSUES OF DUCT CLEANING:
Does duct cleaning prevent health problems?
The bottom line is: no one knows. There are examples of ducts that have become badly contaminated with a variety of materials that may pose risks to your health. The duct system can serve as a means to distribute these contaminants throughout a home. In these cases, duct cleaning may make sense. However, a light amount of household dust in your air ducts is normal. Duct cleaning is not considered to be a necessary part of yearly maintenance of your heating and cooling system, which consists of regular cleaning of drain pans, and heating and cooling coils, regular filter changes and yearly inspections of heating equipment. Research continues in an effort to evaluate the potential benefits of air duct cleaning.

Are duct materials other than bare sheet metal ducts more likely to be contaminated with mold and other biological contaminants?
You may be familiar with air ducts that are constructed of sheet metal. However, many modern residential air duct systems are constructed of fiber glass duct board or sheet metal ducts that are lined on the inside with fiber glass duct liner. Since the early 1970's, a significant increase in the use of flexible duct, which generally is internally lined with plastic or some other type of material, has occurred. The use of insulated duct material has increased due to improved temperature control, energy conservation, and reduced condensation. Internal insulation provides better acoustical (noise) control. Flexible duct is very low cost. These products are engineered specifically for use in ducts or as ducts themselves, and are tested in accordance with standards established by Underwriters Laboratories (UL), the American Society for Testing and Materials (ASTM), and the National Fire Protection Association (NFPA).

Many insulated duct systems have operated for years without supporting significant mold growth. Keeping them reasonably clean and dry is generally adequate. However, there is substantial debate about whether porous insulation materials (e.g., fiber glass) are more prone to microbial contamination than bare sheet metal ducts. If enough dirt and moisture are permitted to enter the duct system, there may be no significant difference in the rate or extent of microbial growth in internally lined or bare sheet metal ducts. However, treatment of mold contamination on bare sheet metal is much easier. Cleaning and treatment with an EPA-registered biocide are possible. Once fiberglass duct liner is contaminated with mold, cleaning is not sufficient to prevent re-growth and there are no EPA-registered biocides for the treatment of porous duct materials. EPA, NADCA, and NAIMA all recommend the replacement of wet or moldy fiber glass duct material.

In the meantime experts do agree that moisture should not be present in ducts and if moisture and dirt are present, the potential exists for biological contaminants to grow and be distributed throughout the home. Controlling moisture is the most effective way to prevent biological growth in all types of air ducts.

Correct any water leaks or standing water. Remove standing water under cooling coils of air handling units by making sure that drain pans slope toward the drain. If humidifiers are used, they must be properly maintained. Air handling units should be constructed so that maintenance personnel have easy, direct access to heat exchange components and drain pans for proper cleaning and maintenance. Fiber glass, or any other insulation material that is wet or visibly moldy (or if an unacceptable odor is present) should be removed and replaced by a qualified heating and cooling system contractor. Steam cleaning and other methods involving moisture should not be used on any kind of ductwork.

DUCT SEALING:
Duct Sealing is the sealing of leaks in air ducts in order to reduce air leakage, optimize efficiency, and control entry of pollutants into the home or building. Air pressure combined with air duct leakage can lead to a loss of energy in a HVAC system and duct sealing solves issues of energy loss in the system.

Duct tape is not used for sealing ducts. Building codes call for special fire-resistant tapes, often with foil backings and long lasting adhesives.

Signs of leaky or poorly performing air ducts include:

  • Utility bills in winter and summer months above average relative to rate fluctuation
  • Spaces or rooms that are difficult to heat or cool
  • Duct location in an attic, attached garage, leaky floor cavity, crawl space or unheated basement.[9][9]



REFERENCES:
1.       http://en.wikipedia.org/wiki/Duct_(HVAC)  (retrieved April 2, 2011)
2.       The Fundamentals volume of the ASHRAE Handbook, ASHRAE, Inc., Atlanta, GA, USA, 2005
3.       HVAC Systems -- Duct Design, 3rd Ed., SMACNA, 1990
4.       "Factory-Made Air Ducts and Air Connectors UL 181", UL Standards, retrieved September 2, 2009 From: http://ulstandardsinfonet.ul.com/scopes/scopes.asp?fn=0181.html
5.       Designer's Guide to Ceiling-Based Room Air Diffusion, Rock and Zhu, ASHRAE, Inc., Atlanta, GA, USA, 2002
6.       "Should You Have the Air Ducts in Your Home Cleaned?", U.S. Environmental Protection Agency, retrieved April 17, 2008 From: http://www.epa.gov/iaq/pubs/airduct.html
7.       "Should You Get Your Heating Ducts Cleaned?", Canadian Mortgage and Housing Corporation, retrieved April 17, 2008 From: http://www.cmhc-schl.gc.ca/en/co/maho/gemare/gemare_011.cfm
8.       Air Conditioning Explained, retrieved 27 July 2009 From: http://airconditioningexplained.com/?p=15


[2] The Fundamentals volume of the ASHRAE Handbook, ASHRAE, Inc., Atlanta, GA, USA, 2005
[3] HVAC Systems -- Duct Design, 3rd Ed., SMACNA, 1990
[4] "Factory-Made Air Ducts and Air Connectors UL 181", UL Standards, retrieved September 2, 2009 From: http://ulstandardsinfonet.ul.com/scopes/scopes.asp?fn=0181.html
[5] Designer's Guide to Ceiling-Based Room Air Diffusion, Rock and Zhu, ASHRAE, Inc., Atlanta, GA, USA, 2002
[6] "Should You Have the Air Ducts in Your Home Cleaned?", U.S. Environmental Protection Agency, retrieved April 17, 2008 From: http://www.epa.gov/iaq/pubs/airduct.html
[7] "Should You Get Your Heating Ducts Cleaned?", Canadian Mortgage and Housing Corporation, retrieved April 17, 2008 From: http://www.cmhc-schl.gc.ca/en/co/maho/gemare/gemare_011.cfm
[8] Air Conditioning Explained, retrieved 27 July 2009 From: http://airconditioningexplained.com/?p=15

AIR COOLING, CENTRAL AIR-CONDITIONING AND FAN COIL UNITS

AR-461: BUILDING SCIENCE
By:
RAVINDAR KUMAR
Assistant Professor
Department of Architecture and Planning
NED University of Engineering and Technology
Karachi
LECTURE NO. 07
TOPIC:             AIR COOLING, CENTRAL AIR-CONDITIONING AND FAN COIL UNITS

INTRODUCTION:
‘Air cooling is a method of dissipating heat. It works by making the object to be cooled have a larger surface area or have an increased flow of air over its surface, or both. An example of the former is to add fins to the surface of the object, either by making them integral or by attaching them tightly to the object's surface (to ensure efficient heat transfer). In the case of the latter it is done by using a fan blowing air into or onto the object one wants to cool. In many cases the addition of fins adds to the total surface area making a heat sink that makes for greater efficiency in cooling. In all cases, the air has to be cooler than the object or surface from which it is expected to remove heat. This is due to the second law of thermodynamics, which states that heat will only move spontaneously from a hot reservoir (the heat sink) to a cold reservoir (the air).’[1]

‘Central air conditioning, commonly referred to as central air (U.S.) or air-con (UK), is an air conditioning system that uses ducts to distribute cooled and/or dehumidified air to more than one room, or uses pipes to distribute chilled water to heat exchangers in more than one room, and which is not plugged into a standard electrical outlet. With a typical split system, the condenser and compressor are located in an outdoor unit; the evaporator is mounted in the air handler unit. With a package system, all components are located in a single outdoor unit that may be located on the ground or roof. Central air conditioning performs like a regular air conditioner but has several added benefits: When the air handling unit turns on, room air is drawn in from various parts of the building through return-air ducts. This air is pulled through a filter where airborne particles such as dust and lint are removed. Sophisticated filters may remove microscopic pollutants as well. The filtered air is routed to air supply ductwork that carries it back to rooms. Whenever the air conditioner is running, this cycle repeats continually. Because the condenser unit (with its fan and the compressor) is located outside the home, it offers a lower level of indoor noise than a free-standing air conditioning unit.’[2]

‘A fan coil unit (FCU) is a simple device consisting of a heating or cooling coil and fan. It is part of an HVAC system found in residential, commercial, and industrial buildings. Typically a fan coil unit is not connected to ductwork, and is used to control the temperature in the space where it is installed, or serve multiple spaces. It is controlled either by a manual on/off switch or by thermostat. Due to their simplicity, fan coil units are more economical to install than ducted or central heating systems with air handling units. However, they can be noisy because the fan is within the same space. Unit configurations are numerous including horizontal (ceiling mounted) or vertical (floor mounted).’[3]
DESIGN AND OPERATION OF FAN COIL UNIT:[4]
It should be first appreciated that 'Fan Coil Unit' is a generic term that is applied to a range of products. Also, the term 'Fan Coil Unit' will mean different things to users, specifiers and installers in different countries and regions, particularly in relation to product size and output capability.

A fan coil unit may be concealed or exposed within the room or area that it serves.

An exposed fan coil unit may be wall mounted, freestanding or ceiling mounted, and will typically include an appropriate enclosure to protect and conceal the fan coil unit itself, with return air grille and supply air diffuser set into that enclosure to distribute the air.

A concealed fan coil unit will typically be installed within an accessible ceiling void or services zone. The return air grille and supply air diffuser, typically set flush into the ceiling, will be ducted to and from the fan coil unit and thus allows a great degree of flexibility for locating the grilles to suit the ceiling layout and/or the partition layout within a space. It is quite common for the return air not to be ducted and to use the ceiling void as a return air plenum.

The coil receives hot or cold water from a central plant, and removes heat from or adds heat to the air through heat transfer. Traditionally fan coil units can contain their own internal thermostat, or can be wired to operate with a remote thermostat. However, and as is common in most modern buildings with a Building Energy Management System (BEMS), the control of the fan coil unit will be by a local digital controller or outstation (along with associated room temperature sensor and control valve actuators) linked to the BEMS via a communication network, and therefore adjustable and controllable from a central point, such as a supervisors head end computer.

Fan coil units circulate hot or cold water through a coil in order to condition a space. The unit gets its hot or cold water from a central plant, or mechanical room containing equipment for removing heat from the central building's closed-loop. The equipment used can consist of machines used to remove heat such as a chiller or a cooling tower and equipment for adding heat to the building's water such as a boiler or a commercial water heater.

Fan coil units are divided into two types:
  1. Two-pipe fan coil units
Two-pipe fan coil units have one (1) supply and one (1) return pipe. The supply pipe supplies either cold or hot water to the unit depending on the time of year.
  1. Four-pipe fan coil units
Four-pipe fan coil units have two (2) supply pipes and two (2) return pipes. This allows either hot or cold water to enter the unit at any given time. Since it is often necessary to heat and cool different areas of a building at the same time, due to differences in internal heat loss or heat gains, the four-pipe fan coil unit is most commonly used.

Fan coil units may be connected to piping networks using various topology designs, such as "direct return", "reverse return", or "series decoupled". See ASHRAE Handbook "2008 Systems & Equipment", Chapter 12.
Depending upon the selected chilled water temperatures and the relative humidity of the space, it is likely that the cooling coil will dehumidify the entering air stream, and as a byproduct of this process, it will at times produce a condensate which will need to be carried to drain. The fan coil unit will contain a purpose designed drip tray with drain connection for this purpose. The simplest means to drain the condensate from multiple fan coil units will be by a network of pipe work laid to falls to a suitable point. Alternatively a condensate pump may be employed where space for such gravity pipe work is limited.

Speed control of the fan motors within a fan coil unit is effectively used to control the heating and cooling output desired from the unit. This is normally achieved by manually adjusting the taps on an AC transformer supplying the power to the fan motor. Typically this is adjusted at the commissioning stage of the building construction process and is therefore set for life. However alternative means of external speed control by electronic means through the BEMS can be provided if so required. Fan motors are typically AC type motors but more recently DC motors have been made available by some manufacturers, particularly in the UK, which do offer significant energy savings.

DC \ EC MOTOR POWERED FAN COIL UNITS:[5]
These motors are sometimes called DC motors, sometimes called EC motors and occasionally EC/DC motors. DC stands for Direct Current and EC stands for Electronically Commutated.

DC motors allow the speed of the fans within a Fan Coil Unit to be controlled by means of a 0-10 Volt input 'Signal' to the motor/s, the transformers and speed switches associated with AC Fan Coils are not required. Up to a signal voltage of 2.5Volts (which may vary with different fan / motor manufacturers) the fan will be in a stopped condition but as the signal voltage is increased, the fan will seamlessly increase in speed until the maximum is reached at a signal Voltage of 10 Volts. Fan Coils will generally operate between approximately 4 Volts and 7.5 Volts because below 4 Volts the air volumes are ineffective and above 7.5 Volts the Fan Coil is likely to be too noisy for most commercial applications.

The 0-10 Volt signal voltage can be set via a simple potentiometer and left or the 0-10 Volt signal voltage can be delivered to the fan motors by the terminal controller on each of the Fan Coil Units. The former is very simple and cheap but the later opens up the opportunity to continuously alter the fan speed depending on various external conditions / influences. These conditions / criteria could be the 'real time' demand for heating or cooling, occupancy levels, window switches, time clocks or any number of other inputs from the unit itself, the Building Management System or both.

The reason that these DC Fan Coil Units are, despite their apparent relative complexity, becoming more popular is their improved energy efficiency levels compared to their AC motor driven counterparts of only a few years ago. A straight swap, AC to DC, will reduce electrical consumption by 50% but applying Demand and Occupancy dependant fan speed control can take the savings to as much as 80%. In areas of the world where there are legally enforceable energy efficiency requirements for Fan Coils (such as the UK), DC Fan Coil Units are rapidly becoming the only choice.

AREAS OF USE FOR FAN COIL UNITS:
Fan coil units are typically used in spaces where economic installations are preferred such as unoccupied storage rooms, corridors, loading docks.

In high-rise buildings, fan coils may be stacked, located one above the other from floor to floor and all interconnected by the same piping loop.

Fan coil units are an excellent delivery mechanism for hydronic chiller boiler systems in large residential and light commercial applications. In these applications the fan coil units are mounted in bathroom ceilings and can be used to provide unlimited comfort zones - with the ability to turn off unused areas of the structure to save energy.

INSTALLATION OF FAN COIL UNITS:[6]
In high-rise residential construction, typically each fan coil unit requires a rectangular through-penetration in the concrete slab on top of which it sits. Usually, there are either 2 or 4 pipes made of ABS, steel or copper that goes through the floor. The pipes are usually insulated with refrigeration insulation, such as acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam on all pipes or at least the cool lines.

UNIT VENTILATOR:[7]
A unit ventilator is a fan coil unit that is used mainly in classrooms, hotels, apartments and condominium applications. A unit ventilator can be a wall mounted or ceiling hung cabinet, and is designed to use a fan to blow air across a coil, thus conditioning the space which it is serving.

REFERENCES:
1.       http://en.wikipedia.org/wiki/Air_cooling (retrieved April 2, 2011)
3.       http://en.wikipedia.org/wiki/Fan_coil_unit (retrieved April 2, 2011)